ACH550-PCR/PDR User’s Manual 3-21
Technical data
Fuses, 600 volt, fuses
1. “PxR” represents both PCR and PDR.
2. UL Type / NEMA 3R enclosed units are provided with Bussman Type JJS or equivalent fuses. Fuse
ratings shown relate to latest production. Where installed product includes fuses of a lower rating, either
rating may be used.
600 Volt
Frame
Size
Drive Input Fuse Ratings
HP Type Code
1
Amps
(600V)
Bussmann
Type
2 ACH550-PDR-02A7-6 R2 15 KTK-R-15
3 ACH550-PDR-03A9-6 R2 15 KTK-R-15
5 ACH550-PDR-06A1-6 R2 15 KTK-R-15
7.5 ACH550-PDR-09A0-6 R2 15 KTK-R-15
10 ACH550-PDR-011A-6 R2 30 KTK-R-30
15 ACH550-PDR-017A-6 R2 30 KTK-R-30
20 ACH550-PDR-022A-6 R3 60 JJS-60
25 ACH550-PDR-027A-6 R3 60 JJS-60
30 ACH550-PDR-032A-6 R4 100 JJS-100
40 ACH550-PDR-041A-6 R4 100 JJS-100
50 ACH550-PDR-052A-6 R4 100 JJS-100
60 ACH550-PDR-062A-6 R4 100 JJS-100
75 ACH550-PxR-077A-6 R6 200
170M1370
2
or 170M2617
100 ACH550-PxR-099A-6 R6 200
170M1370
2
or 170M2617
125 ACH550-PxR-125A-6 R6 200
170M1370
2
or 170M2617
150 ACH550-PxR-144A-6 R6 200
170M1370
2
or 170M2617