1-88 ACH550-UH User’s Manual
Parameters
0303 FB STS WORD 1 - 1 -
Read-only copy of the Status Word 1.
The drive sends status information to the fieldbus controller. The status consists of two Status Words.
The control panel displays the word in hex. For example, all zeros and a 1 in Bit 0 displays as 0001. All zeros and
a 1 in Bit 15 displays as 8000.
0304 FB STS WORD 2 - 1 -
Read-only copy of the Status Word 2.
See parameter 0303.
Group 03: Actual Signals
Code Description Range Resolution Default S
Bit # 0303, FB STS WORD 1 0304, FB STS WORD 2
0 READY ALARM
1 ENABLED NOTICE
2 STARTED DIRLOCK
3 RUNNING LOCALLOCK
4 ZERO_SPEED CTL_MODE
5 ACCELERATE Reserved
6 DECELERATE Reserved
7 AT_SETPOINT CPY_CTL
8 LIMIT CPY_REF1
9 SUPERVISION CPY_REF2
10 REV_REF REQ_CTL
11 REV_ACT REQ_REF1
12 PANEL_LOCAL REQ_REF2
13 FIELDBUS_LOCAL REQ_REF2EXT
14 EXT2_ACT ACK_STARTINH
15 FAULT ACK_OFF_ILCK