1-90 ACH550-UH User’s Manual
Parameters
0308 ALARM WORD 1 - 1 -
When an alarm is active, the corresponding bit for the active alarm is set in the Alarm Words.
Each alarm has a dedicated bit allocated within Alarm Words.
Bits remain set until the whole alarm word is reset. (Reset by writing zero to the word.)
The control panel displays the word in hex. For example, all zeros and a 1 in Bit 0 displays as 0001. All zeros and
a 1 in Bit 15 displays as 8000.
0309 ALARM WORD 2 - 1 -
See parameter 0308.
Group 03: Actual Signals
Code Description Range Resolution Default S
Bit # 0308, ALARM WORD 1 0309, ALARM WORD 2
0 OVERCURRENT Reserved
1 OVERVOLTAGE PID SLEEP
2 UNDERVOLTAGE ID RUN
3 DIR LOCK Reserved
4 IO COMM START ENABLE 1 MISSING
5 AI1 LOSS START ENABLE 2 MISSING
6 AI2 LOSS EMERGENCY STOP
7 PANEL LOSS ENCODER ERROR
8 DEVICE OVERTEMP FIRST START
9 MOTOR TEMP Reserved
10 Reserved USER LOAD CURVE
11 MOTOR STALL START DELAY
12 AUTORESET Reserved
13 AUTOCHANGE Reserved
14 PFA I LOCK Reserved
15 Reserved Reserved