ACH550-UH User’s Manual 1-93
Parameters
10 = COMM – Assigns the fieldbus Command Word as the source for the start/stop and direction commands.
Bits 0, 1, 2 of Command Word 1 (parameter 0301) activates the start/stop and direction commands.
See Fieldbus user’s manual for detailed instructions.
11 =
TIMED FUNC 1. – Assigns Start/Stop control to Timed Function 1 (Timed Function activated = START; Timed
Function de-activated =
STOP). See Group 36: TIMED FUNCTIONS.
12…14 =
TIMED FUNC 2…4 – Assigns Start/Stop control to Timed Function 2…4. See TIMED FUNC 1 above.
1002 EXT2 COMMANDS 0…14 1 1 (
DI1)
Defines external control location 2 (
EXT2) – the configuration of start, stop and direction commands.
See parameter 1001
EXT1 COMMANDS above.
1003 DIRECTION 1…3 1 1 (
FORWARD)
Defines the control of motor rotation direction.
1 = FORWARD – Rotation is fixed in the forward direction.
2 =
REVERSE – Rotation is fixed in the reverse direction.
3 =
REQUEST – Rotation direction can be changed on command.
Group 10: Start/Stop/Dir
Code Description Range Resolution Default S