18 ACH580 E-Clipse bypass and packaged drive user manual
Installation
Basic control connections for E-Clipse HVAC Default
Parameters Changed Relative to E-Clipse HVAC Default
Smoke Control (Override1) is a fixed input. Closing Digital Input 6 will place the E-Clipse Bypass in Smoke
Control mode which may reassign the function of the other Digital Inputs. Refer to the Smoke Control
(Override1) documentation.
Parameter Number Description Setting
1
X2
+24Vdc
2
+24Vdc
3
Digital Input Common
4
GND
5
Digital Input 1 (Parameter 1601) START/STOP
6
Digital Input 2 (Parameter 1602,06) NOT SEL
7
Digital Input 3 (Parameter 1603) START INTERLOCK 1
8
Digital Input 4 (Parameter 1604,07) NOT SEL
9
Digital Input 5
(Parameter 1605, 1701)
NOT SEL
Digital Input 6 (Fixed)
SMOKE CONTROL*
(OVERRIDE 1)
10
11
X2
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Relay Output 1 (parameter 1401) BYP NOT FLT
Default Operation: Bypass Not Faulted 11 connected to 13
Bypass Faulted 11 connected to 12
Relay Output 2 (parameter 1404) SYS RUNNING
Default Operation: System Running 14 connected to 16
Relay Output 3 (parameter 1407) SYS STARTED
Default Operation: System started 17 connected to 19
Relay Output 4 (parameter 1410) BYPASS SEL
Default Operation: Bypass selected 20 connected to 22
Relay Output 5 (parameter 1413) BYPASS AUTO
Default Operation: Bypass auto 23 connected to 25
1
2
3
4
5
6
7
8
9
Terminal for Signal Cable Shield
Analog Input 1
Analog Input Common
+10V Reference Voltage for Potentiometer
Analog Input 2
Analog Input Common
Analog Output 1
Analog Output 2
Analog Output Common
ACH580 CONTROL BOARD
E-CLIPSE BYPASS CONTROL BOARD
X1
+
-

Table of Contents