ACH580 E-Clipse bypass and packaged drive user manual 179
Fieldbus adapter
Reference
As described earlier in Control interface, the REFERENCE word is a speed or
frequency reference.
Reference scaling
The following table describes REFERENCE scaling for the ABB Drives profile.
Note: The setting of parameter 1104 REF1 MIN and 1107 REF2 MIN has no effect
on the scaling of references.
ABB Drives Profile (FBA)
Reference Range
Reference
Type
Scalar Remarks
REF1
-32767…
+32767
Frequency -20000 = -(par 46.02)
+20000 = (par 46.02)
Final reference limited by
30.13/30.14
Speed -20000 = -(par 46.01)
+20000 = (par 46.01)
Final reference limited by
30.11/30.12
REF2
-32767…
+32767
Frequency -20000 = -(par 46.02)
+20000 = (par 46.02)
Final reference limited by
30.13/30.14
Speed -20000 = -(par 46.01)
+20000 = (par 46.01)
Final reference limited by
30.11/30.12