70 ACH580 E-Clipse bypass and packaged drive user manual
Parameters
Group 51: External Comm Mode
Group 52: FBA Data In
Group 51: External Comm Mode
Code Name Resolution Range Default Description
5101 FBA TYPE 1 0 = NOT DEFINED
1 = Profibus
15 = LonWorks
37 = DeviceNet
502 = Modbus TCP
2222 Ethernet/IP
Displays type of attached
fieldbus adapter module.
5102
...
5126
FBA PAR 2
...
FBA PAR 26
1 0 - 65535 0 Fieldbus specific - consult FBA
User’s Manual.
5127 REFRESH 1 0 = DONE
1 = REFRESH
0 Validates any changed adapter
module configuration
parameters. After refreshing,
value reverts automatically to
DONE.
5128 FBA PAR 28 1 0 - 0xFFFF 0 Parameter table version
5129 FBA PAR 29 1 0 - 0xFFFF 0 Bypass type code
5130 FBA PAR 30 1 0 - 0xFFFF 0 Mapping file version
5131 FBA PAR 31 1 0 - 6 0 Fieldbus adapter status
5132 FBA PAR 32 1 0 - 0xFFFF 0 Module common software
version
5133 FBA PAR 33 0 - 0xFFFF 0 Module application software
version
Group 52: FBA Data In
Code Name Resolution Range Default Description
5201
...
5210
DATA IN 1
...
DATA IN 10
1 0 = Not In Use
1 = Control Word (ABBDP)
2 = Ref 1 (ABBDP)
3 = Ref 2 (ABBDP)
4 = Status Word (ABBDP)
5 = Actual Value 1 (ABBDP)
6 = Actual Value 2 (ABBDP)
0101h -063FFh = Drive
parameters
8101h - E3FFh = Bypass
parameters + 8000h
0 Specifies information to be
read from the drive (into
the network). Only for
modules that support the
cyclic low scanner function
(such as FMBT-12).
For specifying values 1-6,
select ABB drive’s profile
information, like status
word or actual values.
To specify drive
parameters, use the format
ggh.pph where gg
h
is the
parameter group in
hexadecimal and pp
h
is
the parameter in
hexadecimal.
For instance, drive
parameter 30.14 is
encoded as 1E0Eh.
Bypass parameter is
specified as 8000h +
gg
h
.pp
h
. For instance,
bypass parameter 0114 is
encoded as 810Eh.

Table of Contents