Go to Menu Primary settings. Set the start/stop and reference, motor data, ramps
and limits. You can continue with further adjustment. See in the firmware manual or
press the information on Primary settings menu items.
5. Commissioning with parameters (advanced users only):
Go to Menu Parameters Complete list. See chapter Parameters in the firmware
manual.
HVAC quick commissioning
In the Main menu, select Primary settings and press
(Select) to enter the Primary settings menu.
Select HVAC quick setup and press (Select) (or ).
Go through the items on the menu.
To adjust the value of a parameter, press (Edit), adjust
the value using , , and keys and press
(Save). Note that the actual wiring must match the new
value.
Go back to the Main menu by pressing (Back) re-
peatedly.
10 EN Quick start-up guide