ACH580 E-Clipse bypass and packaged drive user manual 93
Embedded fieldbus
Bypass relay output control
Using the fieldbus for relay output control requires:
Bypass parameter values set as defined below.
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
For example: To control relays 1 and 2 using serial communication:
From the bypass keypad, set parameters 1401
RELAY OUTPUT 1 and 1402 RELAY
OUTPUT 2 = 16 (COMM CTRL).
Then, for example using N2:
To turn Relay 1 On: Force object BO5 to On.
To turn Relay 2 On: Force object BO6 to On.
To turn both Relay 1 and 2 On: Force objects BO5 and BO6 On.
Note: Relay status feedback occurs without configuraton as defined below
.
Bypass
Parameter
Value Setting
Protocol Reference
Modbus
N2 BACnet
1625 =
“SYSTEM”
1
1625 =
“DRIVE
ONLY”
2
1401 RELAY
OUTPUT 1
16
(Comm
Ctrl)
Relay Output 1
controlled by fieldbus.
400263 bit 0 433031 bit 0 BO5 BO0
1404 RELAY
OUTPUT 2
16
(Comm
Ctrl)
Relay Output 2
controlled by fieldbus.
400263 bit 1 433031 bit 1 BO6 BO1
1407 RELAY
OUTPUT 3
16
(Comm
Ctrl)
Relay Output 3
controlled by fieldbus.
400263 bit 2 433031 bit 2 BO7 BO2
1410 RELAY
OUTPUT 4
16
(Comm
Ctrl)
Relay Output 4
controlled by fieldbus.
400263 bit 3 433031 bit 3 BO8 BO3
1413 RELAY
OUTPUT 5
16
(Comm
Ctrl)
Relay Output 5
controlled by fieldbus.
400263 bit 4 433031 bit 4 BO9 BO4
1) Written via Bypass node.
2) Written via Drive node.
Bypass Parameter Value N2 BACnet
0104 RO Status RO 1-5 STATUS Relay 1…5 status. B10…B14 B10…B14