116 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
BACnet Device Address Rules
OWS
(Operator
Workstation)
Router 1
Router 2
VAV1 VAV2
VAV3
ACH 580
Drive
Bypass
IP
MSTP
MSTP
MSTP MAC=1
(param 58.03 = 1)
DeviceOID=3001
(param 58.40 = 3001)
(param 58.99 = 0)
MSTP MAC = 2
(bypass param 5803 = 2)
DeviceOID = 3002
(bypass param 58.40 = 3002)
(bypass param 58.99 = 0)
MSTPNetwork#=3
MSTP MAC=0
DeviceOID=3000
IP Network#=1
MSTP MAC=1
DeviceOID=2001
MSTP MAC=2
DeviceOID=2002
MSTP MAC=3
DeviceOID=2003
MSTP Network#=2
MSTP MAC=0
DeviceOID=2000
IP Network#=1
-- MSTP MAC Addresses must be unique for all devices connected to the same RS485 network.
-- MSTP MAC Address is configurable via parameter 5003 in the bypass.
1..127 = range of supported Master addresses for the bypass
-- Network Number must be unique for each network (IP and MSTP)
-- Network Number of 0 is reserved for broadcasts
-- Device Object IDs must be unique across the entire BACnet network, all IP and MSTP subnetworks.
-- Device Object IDs are 22 bits, configurable via parameters 5840 and 5899 in the bypass.
-- The example Network Numbers and DeviceOIDs show a good way to maintain unique DeviceOIDs
across the network.
IP Network#=1
E-Clipse
MSTP MAC = 3
(bypass param 5003 = 3)
DeviceOID = 3003
(bypass param 50.40 = 3003)
(bypass param 50.99 = 0)