130 ACH580 E-Clipse bypass and packaged drive user manual
Embedded fieldbus
AV13 EXT PID DEV This object is the External PID output
signal’s deviation from its setpoint.
Calculated as (drive parameter 71.04) /
drive parameter 71.14).
Percent R
AV14 RUN TIME (R) This object indicates, in hours, the drive’s
accumulated run time since the last reset.
The value can be reset to zero. The
corresponding drive parameter is 05.03.
Hours W
AV15 MOTOR TEMP This object indicates the drive’s motor
temperature, as set up in parameter
Group 35. The corresponding drive
parameter is 35.02 or 35.03 if either
enabled or 35.01.
°C R
AV16 INPUT REF 1 This object sets 03.09. Group 22 must be
configured to make use of EFB ref 1.
Percent C
AV17 INPUT REF 2 • This object sets 03.10. Group 22 must
be configured to make use of EFB
ref 2.
Percent C
AV18 LAST FLT This object indicates the most recent fault
entered in the drive’s fault log.
None R
AV19 PREV FLT 1 This object indicates the second most
recent fault entered in the drive’s fault
log.
None R
AV20 PREV FLT 2 This object indicates the third most recent
fault entered in the drive’s fault log.
None R
AV21 AO 1 ACT This object indicates Analog Output 1’s
level. The corresponding drive parameter
is 12.11. Units depend on drive
parameter 12.15.
mA or V R
AV22 AO 2 ACT This object indicates Analog Output 2’s
level. The corresponding drive parameter
is 12.22. Units depend on drive
parameter 12.25.
mA or V R
AV23 ACCEL1 TIME This object sets the Ramp1 acceleration
time. The corresponding drive parameter
is 28.72 if 99.04 value = Scalar; 23.12 if
99.04 value = Vector.
Seconds W
AV24 DECEL1 TIME This object sets the Ramp1 deceleration
time. The corresponding drive parameter
is 28.73 if 99.04 value = Scalar; 23.13 if
99.04 value = Vector.
Seconds W
AV25 MBOX PARAM This object defines the parameter to be
read or written to by the mailbox function.
See BV15 and BV16.
None W
AV26 MBOX DATA This object holds the mailbox function’s
parameter value – a value that was read,
or is to be written. See BV15 and BV16.
None W
AV29 FRQ OUT MIN This object indicates the drive’s minimum
output frequency.
Amps R
AV30 FRQ OUT MAX This object indicates the drive’s
maximum output frequency.
Percent R
Instance
ID
Object Name Description Units
Present Value