64 ACH580 E-Clipse bypass and packaged drive user manual
Parameters
Group 16: System Control
1411 R4 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to
active output.
1412 R4 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state
to inactive output.
1413 RO5 SELECT 1 See RO 1 Select. BYPASS
AUTO
(13)
1414 R5 ON DLY 0.1 sec 0-3600.0s 0s Delay from active state to
active output.
1415 R5 OFF DLY 0.1 sec 0-3600.0s 0s Delay from inactive state
to inactive output.
Group 16: System Control
Code Name Resolution Range Default Description
1601 START/STOP 1 0 = NOT SEL
1 = DI1
2 = COMM
DI 1
(1)
Selects source for system start
command.
1602 PERMISSIVE 1 0 = NOT SEL
1 = DI2
2 = COMM
NOT SEL
(0)
Selects source for the
permissive command.
1603 INTERLOCK 1 1 0 = NOT SEL
1 = DI3
2 = COMM
DI 3
(1)
Selects source for the interlock 1
command.
1604 INTERLOCK 2 1 0 = NOT SEL
1 = DI4
2 = COMM
NOT SEL
(0)
Selects source for the interlock 2
command.
1605 INTERLOCK 3 1 0 = NOT SEL
1 = DI5
2 = COMM
NOT SEL
(0)
Selects source for the interlock 3
command.
1606 INTERLOCK 4 1 0 = NOT SEL
1 = DI2
2 = COMM
NOT SEL
(0)
Selects source for the interlock 4
command.
1607 RESET SRC 1 0 = NOT SEL
1 = DI4
2 = COMM
NOT SEL
(0)
Selects source for fault reset
command (rising edge).
1608 AUTO XFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Enabled allows auto transfer to
bypass on all drive faults except
the conditional faults which
require an additional enable.
NOT SEL prevents auto transfer
to bypass for all drive faults
including the conditional faults.
1609 OC TRANSFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive over current causes auto
transfer. Requires global auto
transfer enable also.
1610 OV TRANSFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive over voltage causes auto
transfer. Requires global auto
transfer enable also.
1611 UV TRANSFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive under voltage causes auto
transfer. Requires global auto
transfer enable also.
1612 AI TRANSFR 1 0 = NOT SEL
1 = ENABLE
NOT SEL
(0)
Drive AI loss causes auto
transfer. Requires global auto
transfer enable also.
1613 BP DISABLE 1 0 = NOT SEL
1 = DISABLE
NOT SEL
(0)
Disables bypass mode.
1614 BP RUN DLY 1 sec 0 - 300 secs 0s Bypass contactor pick-up delay
when starting bypass or
transferring from Drive mode.
1615 SAVE PARAM 1 0 = DONE
1 = SAVE
0 Save User Settings (SaveImm +
SavePwrd).