EasyManua.ls Logo

ABB ACH580-VCR - Serial Communication Configuration - Bypass

ABB ACH580-VCR
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74 ACH580 E-Clipse bypass and packaged drive user manual
Parameters
Group 98: Options
Group 99: Startup Data
Group 98: Options
Code Name Resolution Range Default Description
9802 COMM PROT 1 0=NOT SEL
1=STD MODBUS
2=N2
4=EXT FBA
5=BACNET
0 This parameter sets the
communication protocol that the
package will communicate to the
building automation system.
Group 99: Startup Data
Code Name Resolution Range Default Description
9902 B.P. MACRO 1 1 = HVAC DEFAULT
2 = DAMPER
3 = RETROFIT
4 = SMOKE CONTROL
1 Select bypass macro.
Predefined set of parameter
values for certain application
is loaded in use.

Table of Contents

Other manuals for ABB ACH580-VCR

Related product manuals