Chapter 4 – Programming
4-10 ACS/ACH 400 Direct N2 Bus Interface
FL10 PANEL LOSS Panel loss. Panel is disconnected when Start/Stop/Dir or
reference is coming from panel. See parameter 3002 and
APPENDIX.
Note! If FL10 is active when the power is turned off, the
ACS/ACH 400 will start in remote control (REM) when the
power is turned back on.
FL11 PARAMETERING Parameters inconsistent. Possible fault situations:
•
MINIMUM AI1 > MAXIMUM AI1 (parameters 1301 and
1302)
•
MINIMUM AI2 > MAXIMUM AI2 (parameters 1304 and
1305)
•
MINIMUM FREQ > MAXIMUM FREQ (parameters 2007 and
2008)
FL12 MOTOR STALL Motor stall. See parameter 3009
STALL FUNCTION.
FL13 SERIAL COMM
LOSS
Serial communication loss.
FL14 EXTERNAL
FAULT SIGNAL
External fault is active. See parameter 3003
EXTERNAL
FAULT.
FL15
*
OUTPUT EARTH
FAULT
Output ground fault.
FL16
*
DC BUS RIPPLE DC bus ripple too high. Check power supply for phase
loss or imbalance.
FL17 UNDERLOAD Underload.
FL18 Reserved.
FL19 DDCS LINK DDCS link fault.
FL20
-
FL28
*
HARDWARE
ERROR
Hardware error. Contact the factory.
“COMM LOSS” (ACS-PAN) Serial link failure. Bad connection between the control
panel and the ACS/ACH 400.