Chapter 3 – Electrical Installation
ACS/ACC/ACP 604/607 Drives ACx=ACS/ACC/ACP 3-9
Pulse Encoder
Insulation (ACP600)
The tachometer shall be insulated electrically from stator or rotor to 
prevent forming of current path through the tachometer. The usual 
coupling-type encoder must have an electrically insulating coupling. 
When a hollow-shaft type tachometer is used, the insulation can be 
implemented by insulating the ball joints of the engaging arm, or 
insulating the bar of the engaging arm. Shield of the tachometer cable 
should be insulated from the tachometer frame. The other end of the 
shield is grounded at the converter drive.
Installation of 
Optional Modules and 
Drive Window
This section gives general installation instructions for Drive Window PC 
tool and ACx 600 optional modules, such as fieldbus adapters, I/O 
extension modules and the pulse encoder interface. Connection 
examples are given at the end of the section.
Placement
The module should be installed on the DIN mounting rail inside the 
cabinet. Follow the instructions given in the 
Mechanical Installation 
chapter of the module manual.
Power Supply
for the Module
The 24 V d.c. supply for one optional module is provided by the NIOC/
NIOCP board of the converter (NIOC: terminal X23, NIOCP: terminal 
X4). The location of the NIOC/NIOCP board is shown in the 
dimensional drawings (
Appendix B
).
Fiber Optic Link
Optional modules are connected via a DDCS fiber optic link to the 
NAMC board or NDCO board (mounted on top of the NIOC board). The 
terminals on the NAMC/NDCO board to which the cables are 
connected are as follows:
* on NDCO board when NAMC-1 board is used
Observe color codes when installing fiber optic cables. Blue connectors 
should go to blue terminals, and grey connectors to grey terminals.
In case multiple modules are installed on the same channel, they must 
be connected in a ring.
Module Type Channel Terminals
Fieldbus Adapter Modules CH0 V13*, V14*
I/O Extension Modules CH1 V15, V16
Pulse Encoder Interface Module CH2 with ACS 600 
Standard Application 
Program 5.0
V17, V18
CH1 with ACC Application 
Program
V15, V16
Double Pulse Encoder Interface 
Module (for ACP 600 only)
CH2 V17, V18
Drive
Window
CH3 V19, V20