Appendix C – IEC Installation
ACS/ACC/ACP 604/607 Drives ACx=ACS/ACC/ACP C-5
Mains, Motor and 
Control Cable 
Connection
A view of the recommended earthing, mains and motor cable 
connections of the ACx 607 is presented below. F denotes a 360 
degrees earthing.
ACx 607 
Frequency 
Converter
U1
V1
W1
3 ~
Motor
U2
V2 W2
ACx 604  
Converter Unit
UDC+ UDC-
PE
Line Options
U1
W1
V1
Max 6 control cables
F
1)
2)
1) used if the conductivity of the cable screen is < 
50 % of the conductivity of the phase conductor.
 2) used if the PE rail of ACx 607 is not earthed via 
separate PE conductor or via cable screen.
3) used only if local safety regulations do not accept 
earthing of the ACx 607 and the motor merely 
through the cable screen. 
Note: Connecting the fourth conductor of the 
cable at the motor increases bearing currents, 
thus causing extra wear.
4)  The NIOC/NIOCP board is located inside the 
module in ACx 604 deliveries.
F
U1
W1
V1
L1    L2     L3     PE
T41
X2
F
3)
For minimum radio frequency 
interference (RFI) at the motor 
end, earth the cable screen 360 
degrees at the lead-through or 
earth the cable by twisting the 
screen (flattened width  >
 1/5 · 
length).
du/dt Filter
EMC Line Filter
(option)
NIOC/ NIOCP
NAMC
4)
NIOC/ NIOCP
NAMC