Appendix A – ACS/ACC/ACP 604/607 Technical Data
ACS/ACC/ACP 604/607 Drives ACx=ACS/ACC/ACP A-3
NEMA Ratings
The NEMA ratings for ACS 604 and ACS 607 with 60 Hz supply are
below. Symbols are described on previous page.
Output Current
Temperature Derating
The output current is calculated by multiplying the current given in the
rating table by the derating factor.
Temperature derating factor for ACx 607:
General rule:
Above +40 °C / +104 °F (+35 °C / +95 °F for types
ACS 601-0120-03 and ACS 60x-0140-3 with
I
2Nsq
rating), the rated
output current is decreased 1.5% for every additional 1 °C / 1.8 °F
(up to +50 °C / +122 °F). This applies to
I
2N
and
I
2Nsq
(for
I
2hd
no
derating is needed).
Example 1.
If the ambient temperature is 50 °C / +122 °F the
derating factor is
100% - 1.5 · 10 °C = 85% or 0.85.
The output current is then 0.85 ·
I
2N
or 0.85 ·
I
2Nsq
or 1 ·
I
2hd
.
Normal Use Heavy-duty Use
ACS 604/607
Type
Duty Cycle
1/10 min
Duty Cycle
1/10 min
Duty Cycle
1)
2/15 s
Frame
Type
I
2N
9/10min
[A]
I
2Nmax
1/10min
[A]
P
N
[HP]
I
2hd
9/10min
[A]
I
2hdmax
1/10min
[A]
I
2hd
13/15s
[A]
I
2hdmax
2/15s
[A]
P
hd
[HP]
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
ACS 604/607-0120-4 156 172 125 113 168 113 224 75 R7
ACS 604/607-0140-4 180 198 150 141 203 141 270 100
ACS 604/607-0170-4 216 238 150 172 246 172 328 125 R8
ACS 604/607-0210-4 260 286 200 200 300 200 400 150
ACS 604/607-0260-4 316 348 250 240 360 240 480 200
ACS 604/607-0320-4 414 455 300/350 300 450 300 600 250 R9
ACS 604/607-0400-4 480 528 400 365 548 365 730 300
Note: The US manufactured units are labeled as -4 types. The information in this
manual concerning the corresponding -5 type applies to them.
%