EasyManua.ls Logo

ABB ACS 607 - Control Cable Connection Procedure for ACx 607

ABB ACS 607
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix C – IEC Installation
C-8 ACx=ACS/ACC/ACP ACS/ACC/ACP 604/607 Drives
Control Cable
Connecting Procedure
To connect the control cables for ACx 607 carry out the following
procedure:
1. Loosen the
lead-through plate
position screws
. Pull the two parts
apart.
2. Lead the cable inside the cabinet through the
EMI conductive
cushions.
3. Strip off the cable plastic sheath above the
base plate
(only a
distance wide enough to ensure proper connection of the bare
screen and the
EMI conductive cushions
).
4. Earth the screen between the
EMI conductive cushions
:
a. If the outer surface of the screen is conductive:
- Push the two parts of the
lead-through plate
together so that the
EMI conductive cushions
press tightly round the bare screen.
EMI conductive cushions
Base plate
Holes for
position screws
Side view Top view
Lead-through plate

Table of Contents

Related product manuals