CHAPTER 6 – ELECTRICAL INSTALLATION 104
6. Remove the cable insulation at the point of
entry (1).
If the outer cable screen is non-conductive, cut
open the cable screen in the middle of the
stripped area (1). To turn the conductive side
inside out, pull the cable screen ends over the
cable insulation (2). Connect the screens ends
with a continuous conducting foil (3).
7. Pull the cables through the EMC cushions.