CHAPTER 3 – CONTROL SYSTEM 49
IOEC module configuration
Each IOEC module is configured with both analog
and digital inputs and outputs as shown in
Table 3-1.
24 V internal voltage supply
One isolated DC/DC converter supplies an over-
load protected voltage of 24 V (DC) to operate dig-
ital inputs from passive contacts. The output is
protected by a PTC-resistor against short-circuit
and external applied overvoltages.
Table 3-1 IOEC module configuration
Analog inputs
No. of I/O 4
Resolution 10 bit
Signal interface Floating, galvanically isolated
Signal level 0 - 20 mA, 4 - 20 mA, 0 - 10 V, 2 - 10 V
Individually scalable by parameter
Input resistance R
in
= 105 ? for current input
R
in
= 250 k? for voltage input
Common mode voltage Maximum: 48 V
Isolation level 350 V (AC)
Analog outputs
No. of I/O 2
Signal range 0 - 20 mA (load impedance: max. 250 ?)
Resolution 12 bit
Isolation level 350 V (AC)
Digital inputs
No. of I/O 14
Signal level 22 - 80 V (DC)
22 - 120 V (DC) with IOEC Adapter - 3BHE040914R0101
22 - 250 V (AC)
Logical thresholds
< 13 V (AC or DC)
"0", > 16 V (AC or DC) "1"
Input current 13 mA steady state (14 mA max. inrush) at 24 V (DC)
11.5 mA steady state (80 mA max. inrush) at 120 V (DC)
10.5 mA steady state (92 mA max. inrush) at 230 V (AC)
Isolation level 1350 V (AC)
Digital outputs
No. of I/O 6
Signal level Maximum: 120 V (DC) or 250 V (AC)
Isolation level 4000 V (AC)
Switching capacity Voltage Switching current Steady state current
24 V (DC) 8 A
6 A
24 V (AC) 8 A
48 V (DC) 1 A
48 V (AC) 8 A
120 V (DC) 0.4 A
120 V (AC) 8 A
230 V (AC) 8 A
Table 3-2 24 V internal voltage supply
Output voltage 24 V (unregulated)
Available output current 180 mA