64 ACS2000 DFE UM 3BHS360367 ZAB E01 REV. K
4.5 Storage
The drive can be stored for up to one year in the original packaging as
long as they are not damaged or opened. For information on longer
storage periods, contact the ABB service organization.
4.5.1 Storage conditions
The minimum requirements for storage are based
on
IEC 60721-3-1 'Classification of environmental
conditions: Classification of groups of environ-
mental parameters and their severities; Storage'
Table 4-2 Storage conditions
.
4.5.2 Storage
If the drive is taken out of service for a longer time
proceed as follows:
1. Cover all cable inlets and ventilation slots with
an impermeable plastic or aluminum foil and
a wooden panel.
2. Add a desiccant of the appropriate quality:
- 1 unit desiccant (30g) absorbs 6 g water
vapor.
The following quantity is needed when using
a polyethylene foil:
-10 units/m
2
foil
3. Close and lock the doors of the cabinet.
4. Use polyethylene or equivalent for packaging:
-0,3g/m
2
/24h water vapor diffusion
5. Attach humidity indicators to the packaging.
Check the storage conditions and the packaging
regularly. Repair any damages that occur during
the storage period immediately.
1K22 Climatic conditions
Air temperature -25 – +55 °C (drive)
-5 – +55 °C (spare parts)
Relative humidity 10 – 100%
Absolute humidity 0.5 – 29%
1Z3 Special climatic conditions
Movement of surrounding air 30 m/s
1B1 Biological conditions
Flora Negligible
Fauna Negligible
1M12 Mechanical conditions
Vibration
Acceleration spectral density
0.1 m/s
2
(5 – 200 Hz)