EasyManua.ls Logo

ABB ACS310 - Starting up ACS800 Drives with RMBA-01 Modbus RTU Adapter

ABB ACS310
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRT
U‐17‐ PLCanddrivesintegration
StartingupACS800driveswithRMBA01ModbusRTUadapter
Minimumrequiredparametersettings(basedonfactorydefaultsettings)
Parameter Description Setting Comment
98.02 COMM.MODULE
LINK
STD
MODBUS
Activatesfieldbusmodule
98.07 COMMPROFILE ABBDRIVES Communicationprofile“ABBDrives”
52.01 STATION
NUMBER
[Address] ModbusRTUnodeaddressofthedrive
52.02 BAUDRATE 19.2kbit/s
(example)
Transferrateofthelink.Samebaudratemustbe
definedintheModbusRTUmaster.
52.03 PARITY NONE1STO
PBIT
(example)
Parityandstopbits.Sameparityandstopbitsmustbe
definedintheModbusRTUmaster.
Drivepowerdownandpowerupforthenewfieldbussettingstotakeeffect!
10.01 EXT1
STRT/STP/DIR
COMM.CW Fieldbusinterfaceassourceforstartandstop
11.02 EXT1/EXT2
SELECT
COMM.CW FieldbusinterfaceassourcetoswitchtoEXT2control
location
11.03 EXTREF1SELECT COMM.REF Fieldbusinterfaceassourceforspeedreference
16.04 FAULTRESETSEL COMM.CW Fieldbusinterfaceassourceforfaultreset
92.02 MAINDSACT1 102 Actualspeedvaluetake nfr om01.02
92.02 MAINDSACT2 e.g.105 Actualvalue2.E.gtorquetakenfrom01.05
Optionalparameterse
ttings
30.18 COMMFLTFUNC [optional] Howthedrivereactstoafieldbuscommuni cation
break.
30.19 MAINREFDST
OUT
[optional] Timebetweencommunicationbreakdetectionandthe
selectedaction.
(11.05) EXTREF1
MAXIMUM
[Scalemax] Maxspeed/frequencyscalingvalue(usedinfunction
block/visualizationinput“SPEED_REF_MAX”).Mustbe
lessorequaltodriveparametermaxspeed/frequency.

Other manuals for ABB ACS310

Related product manuals