Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐8‐ PLCanddrivesintegration
FieldbusmodulesforABBdrives
The following ABB drives Modbus RTU modules have an option to activate builtin end termination and pull
up/pulldownresistors.
RMBA01(usedwithforinstanceACS550andACS800)
FSCA01(usedwithforinstanceACS880andACSM1)
ThefollowingABBdrivesModbusRTUmoduledoesnothaveanoptiontoactivatebuil
tinendresistorsincluding
pullup/pulldownresistors.
FMBA01(usedwithforinstanceACS355)
Since the builtin end termination of the modules (RMBA01 and FSCA01) automatically also activates pull
up/pulldownresistors,itisrecommendedtoskipthebuiltinoption.
Itis recomm
ended to connect a separateendtermination resistor to the first node (i.e. the PLC COMinterface)
andthelastnode(i.e.thelastdriveonthebus).
Forconnectionexamples,seechapter“Installationexamples”.
Commonrecommendations
Note!Thefollowingbulletsareonlyrecommendationsandnogeneralrules.
Installationwheretotalcablelengthismorethan50 m
o UseCPUAC500ratherthanAC500eCoorAC500eCowithTK506RS485isolatorforCOM1.
Installationwherethereisariskthatgroundconnectionsindiffer
entnodescouldvaryinvoltagepotential
(typicallyinshipinstallationsorwithcablelengthsmorethan50m).
o UseCPUAC500anddonotconnectgroundcable,onlyshield →2wiresolution,oruseAC500eCo
withTK506RS485isolatorforCOM1.
WhenAC500eCoisused
o Use of 3wire conne
ction is recommended because the COM interface is not optoisolated,
oruseAC500eCowithTK506RS485isolatorforCOM1.
o Use of cable length more than 50m should be realized with repeaters,
oruseAC500eCowithTK506RS485isolatorforCOM1.
Cabletyp
e
o Use only cables with twisted pair wires and braided shields. Foil shields are not robust enough,
cannotbecontactedwellandhavepoorHF(HighFrequency)properties.
o Groundthecableshield directlywithaclipwhenenteringtheswitchgearcabinet.Donotcutthe
shieldun
tilthecablereachestheconnectedmodule.
o TheconnectionbetweenthePEbarandtheshieldbarmusthavelowimpedance.
o UseABBcableTK505whensuitableforeasyinstallation.