Quickstart Guide
ABB PLC and drives integration using Modbus RTU
ModbusRTU‐6‐ PLCanddrivesintegration
Hardwarephysicalconnection
Inthefollowingchapter,physicalconnectionofthehardwarewillbeexplained.
Fieldbusgrounding
For AC500, which has optoisolated COM interfaces, it is recommended not to connect the ground. For AC500
eCo, where the COM interfaces are not optoisolated, it is recommended to connect the ground at one place,
typicallyinthebusmaster.Forconnectionexamples,seechapter“Installationexamples”.
Fieldbusshield
TheshieldshouldalwaysbeconnectedinaModbusRTUline.ThepurposeoftheshieldistoprotectagainstEMC
disturbancesandreflectiononthebusline.Forconnectionexamples,seechapter“Installationexamples”.
Endtermination
Purpose:Toavoidsignalreflections.
Resistorsize:120Ohms,¼W.
Wheretoconnect:Oneresistorineachendofthebusline(firstandlastnode).
Pullup/pulldownresistors
Purpose:Tokeepadefinedhighlevelonthebuswhilethereisnodataexchange.
Resistor size: Depends on bus master (COM) voltage level. 470Ωfor AC500 (5 V output) and 270Ωfor
AC500eCo(3.3Voutput).
Wheretoconnect:Activatepullupandthepu lldow
nresistors,butonly onceoneverybus line,atthebus
master.