30 Start-up and control with I/O
Select the application macro according to which the
control cables are connected.
Continue with the application set-up. After
completing a set-up task, the Start-up assistant
suggests the next one.
• Press (when is highlighted) to
continue with the suggested task.
• Press key to highlight and then press
to move to the following task without doing the
suggested task.
• Press to stop the Start-up assistant.
DIRECTION OF THE MOTOR ROTATION
Check the direction of the motor rotation.
• If the drive is in remote control (REM shown on the
status line), switch to local control by pressing .
• If you are not in the Output mode, press
repeatedly until you get there.
• Increase the frequency reference from zero to a
small value with key .
• Press to start the motor.
• Check that the actual direction of the motor is the
same as indicated on the display ( means
forward and reverse).
• Press to stop the motor.
To change the direction of the motor rotation:
• If parameter 9914 PHASE INVERSION is not
visible, first set parameter 1611 PARAMETER
VIEW to 3 (LONG VIEW).
• Invert the phases by changing the value of
parameter 9914 to the opposite, ie from 0 (NO) to
1 (YES), or vice versa.
• Verify your work by applying input power and
repeating the check as described above.
• Set parameter 1611 back to 2 (SHORT VIEW).
9902 APPLIC MACRO
EXIT SAVE
00:00
PAR EDIT
[1]
HVAC DEFAULT
REM
Do you want to
continue with
EXT1 reference setup?
Continue
Skip
EXIT OK
00:00
REM
CHOICE
DIR
MENU
00:00
LOC
xx.xHz
xx x Hz.
xx A.
xx x %.
forward
direction
reverse
direction
1611 PARAMETER VIEW
CANCEL
SAVE
00:00
PAR EDIT
[3]
LONG VIEW
LOC
9914 PHASE INVERSION
CANCEL SAVE
00:00
LOC
[1]
YES
PAR EDIT