34 Actual signals and parameters in the short view
Default values with different macros
When application macro is changed (9902 APPLIC MACRO), the software updates
the parameter values to their default values. The table below shows the parameter
default values for different macros. For other parameters, the default values are the
same for all macros. See the parameter list starting on page 39 in this manual and
chapter Actual signals and parameters in ACS320 user’s manual (3AUA0000062599
[English]).
Index Name/
Selection
HVAC
DEFAULT
SUPPLY
FAN
RETURN
FAN
CLNG TWR
FAN
CONDENSER BOOSTER
PUMP
PUMP
ALTERNA
INT TIMER
9902 APPLIC
MACRO
1 = HVAC
DEFAULT
2 = SUPPLY
FAN
3=RETUR
N FAN
4 = CLNG
TWR FAN
5 =
CONDENSER
6 =
BOOSTER
PUMP
7 = PUMP
ALTERNA
8 = INT
TIMER
1001 EXT1
COMMANDS
1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 11 = TIMER
1
1002 EXT2
COMMANDS
1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = DI1 1 = TIMER 1
1003 DIRECTION 1 =
FORWARD
1 =
FORWARD
1 =
FORWARD
1 =
FORWARD
1 = FORWARD 1 =
FORWARD
1 =
FORWARD
1 =
FORWARD
1102 EXT1/EXT2
SEL
0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1 0 = EXT1
1103 REF1 SEL 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1 1 = AI1
1106 REF2 SEL 19 =
PID1OUT
19 =
PID1OUT
19 =
PID1OUT
19 =
PID1OUT
19 =
PID1OUT
19 =
PID1OUT
19 =
PID1OUT
19 =
PID1OUT
1201 CONST
SPEED SEL
3 = DI3 3 = DI3 3 = DI3 3 = DI3 3 = DI3 3 = DI3 0 = NOT
SEL
0 = NOT
SEL
1304 MINIMUM AI2 20.0% 20.0% 20.0% 20.0% 20.0% 20.0% 20.0% 20.0%
1401 RELAY
OUTPUT 1
1 = READY 7 =
STARTED
7 =
STARTED
1 = READY 1 = READY 1 = READY 31 = PFA 7 =
STARTED
1601 RUN ENABLE 0 = NOT
SEL
2 = DI2 0 = NOT
SEL
0 = NOT
SEL
0 = NOT SEL 0 = NOT
SEL
0 = NOT
SEL
2 = DI2
1608 START
ENABLE 1
4 = DI4 4 = DI4 4 = DI4 4 = DI4 4 = DI4 4 = DI4 0 = NOT SEL 4 = DI4
1609 START
ENABLE 2
0 = NOT
SEL
5 = DI5 5 = DI5 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 5 = DI5
1805 DO SIGNAL 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN 2 = RUN
2007 MINIMUM
FREQ
0.0 Hz 0.0 Hz 0.0 Hz 20.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz 0.0 Hz
2008 MAXIMUM
FREQ
50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz 50.0 Hz
2101 START
FUNCTION
6 = SCAN
START
6 = SCAN
START
6 = SCAN
START
6 = SCAN
START
6 = SCAN
START
1 = AUTO 1 = AUTO 6 = SCAN
START
2108 START
INHIBIT
0 = OFF 0 = OFF 0 = OFF 0 = OFF 0 = OFF 0 = OFF 0 = OFF 0 = OFF
2201 ACC/DEC 1/2
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT SEL 0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
2202 ACCELER
TIME 1
30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 10.0 s 10.0 s 30.0 s
2203 DECELER
TIME 1
30.0 s 30.0 s 30.0 s 30.0 s 30.0 s 10.0 s 10.0 s 30.0 s
3019 COMM FAULT
TIME
10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s 10.0 s
3415 SIGNAL 3
PARAM
AI 1 AI 1 AI 1 AI 1 AI 1 AI 1 AI 1 AI 1
3416 SIGNAL 3 MIN -100.0% -100.0% -100.0% -100.0% -100.0% -100.0% -100.0% -100.0%
3417 SIGNAL 3
MAX
100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0%
3419 OUTPUT 3
DSP UNIT
mA mA mA mA mA mA mA mA
3420 OUTPUT 3
MIN
0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA 0.0 mA
3421 OUTPUT 3
MAX
20.0 mA 20.0 mA 20.0 mA 20.0 mA 20.0 mA 20.0 mA 20.0 mA 20.0 mA
3601 TIMERS
ENABLE
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT
SEL
0 = NOT SEL 0 = NOT SEL 0 = NOT SEL 1 = DI1