Actual signals and parameters in the short view 41
22 ACCEL/DECEL Acceleration and deceleration times
2202 ACCELER
TIME 1
Defines the acceleration time 1, i.e., the time required for
the speed to change from zero to the speed defined by
parameter 2008 MAXIMUM FREQ.
If the speed reference increases faster than the set
acceleration rate, the motor speed will follow the
acceleration rate.
If the speed reference increases slower than the set
acceleration rate, the motor speed will follow the
reference signal.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to
exceed the drive operating limits.
Actual acceleration time depends on parameter 2204 RAMP
SHAPE 1 setting.
30.0 s
0.0…1800.0 s Time 1 = 0.1 s
2203 DECELER
TIME 1
Defines the deceleration time 1, i.e., the time required for
the speed to change from the value defined by parameter
2008 MAXIMUM FREQ to zero.
If the speed reference decreases slower than the set
deceleration rate, the motor speed will follow the
reference signal.
If the reference changes faster than the set deceleration
rate, the motor speed will follow the deceleration rate.
If the deceleration time is set too short, the drive will
automatically prolong the deceleration in order not to
exceed drive operating limits.
If a short deceleration time is needed for a high inertia
application, note that the ACS320 cannot be equipped with
a brake resistor.
Actual deceleration time depends on parameter 2204
RAMP SHAPE 1 setting.
30.0 s
0.0…1800.0 s Time 1 = 0.1 s
53 EFB PROTOCOL Embedded fieldbus link settings.
5301 EFB
PROTOCOL ID
Contains the identification and program revision of the
protocol.
Note: You can reset this parameter only with parameter
9802 COMM PROT SEL.
Format XXYY hex, where XX = protocol ID and YY =
program revision of the protocol.
0000 hex
0000…
FFFF hex
Protocol identification and program revision. 1 = 1 hex
5302 EFB STATION
ID
Defines the address of the device. Two units with the same
address are not allowed on-line.
1
0…65535 Device address. 1 = 1
5303 EFB BAUD
RATE
Defines the transfer rate of the link. 9.6 kbit/s
1.2...
76.8 kbits/s
Transfer rate of the link. -
Parameters in the short parameter view
No. Name/Value Description Def/FbEq