42 Actual signals and parameters in the short view
5304 EFB PARITY Defines the use of parity and stop bit(s) and the data length.
The same setting must be used in all on-line stations.
8 NONE 1
8 NONE 1 8 data bits, no parity, one stop bit. 0
8 NONE 2 8 data bits, no parity two stop bits. 1
8 EVEN 1 8 data bits, even parity, one stop bit. 2
8 ODD 1 8 data bits, odd parity, one stop bit. 3
5305 EFB CTRL
PROFILE
Selects the communication profile. ABB DRV
LIM
ABB DRV LIM Operation of Control/Status words conforms to ABB Drives
Profile.
0
DCU PROFILE Operation of Control/Status words conforms to 32-bit DCU
profile.
1
ABB DRV
FULL
Operation of Control/Status words conforms to ABB Drives
Profile.
2
5306 EFB OK
MESSAGES
Number of valid messages received by the drive. During
normal operation, this number increases constantly.
0
0...65535 Valid messages received by the drive. 1 = 1
5307 EFB CRC
ERRORS
Number of messages with an CRC (cyclic redundancy
check) error received by the drive. If the number is high,
check CRC calculation for possible errors.
Note: High electromagnetic noise levels generate errors.
0
0...65535 CRC error received by the drive. 1 = 1
5308 EFB UART
ERRORS
Number of messages with a character error received by the
drive.
0
0...65535 Character errors received by the drive. 1 = 1
5309 EFB STATUS Status of the EFB protocol. IDLE
IDLE EFB protocol is configured, but not receiving any messages. 0
EXECUT INIT EFB protocol is initializing. 1
TIME OUT A time-out has occurred in the communication between the
network master and the EFB protocol.
2
CONFIG
ERROR
EFB protocol has a configuration error. 3
OFF LINE EFB protocol is receiving messages that are NOT
addressed to this drive.
4
ON-LINE EFB protocol is receiving messages that are addressed to
this drive.
5
RESET EFB protocol is performing a hardware reset. 6
LISTEN ONLY EFB protocol is in listen-only mode. 7
5310 EFB PAR 10 Selects an actual value to be mapped to Modbus register
40005.
0
5311 EFB PAR 11 Selects an actual value to be mapped to Modbus register
40006.
0
5312 EFB PAR 12 Selects an actual value to be mapped to Modbus register
40007.
0
5313 EFB PAR 13 Selects an actual value to be mapped to Modbus register
40008.
0
Parameters in the short parameter view
No. Name/Value Description Def/FbEq