ACS355 Minimum required parameter settings for PROFINET 
The minimum required parameter settings are based on factory default settings. 
Activates fieldbus module 
Communication profile ABB drives 
192.xxx.xx.xx or any other 
required IP address. 
24 For subnet mask 255.255.255.0 
Updates fieldbus settings (groups 51 to 55) 
Fieldbus interface as a source for start and 
stop. 
Fieldbus interface as a source for speed 
reference 
Fieldbus interface as a source for fault 
reset 
Max speed/frequency scaling value (used 
in function block/visualization input 
SPEED_REF_MAX). Must be less or equal 
to drive parameter max speed/frequency. 
ACS355 More parameters read from drive to PLC (optional) 
Actual value or 
parameter of drive 
GG = parameter group, ii = parameter index 
Example, 0104 = actual current; 0145 = motor temp 
Updates fieldbus settings (groups 51 to 55)