10 Fault tracing
A7C1 FBA A communication
Programmable warning:
50.02 FBA A comm loss
func
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Check status of fieldbus communication.
See user documentation of fieldbus
interface.
Check settings of parameter groups 50
Fieldbus adapter (FBA), 51 FBA A
settings, 52 FBA A data in and 53 FBA A
data out.
Check cable connections.
Check if communication master is able to
communicate.
A7CE EFB comm loss
Programmable warning:
58.14 Communication loss
action
Communication break in
embedded fieldbus (EFB)
communication.
Check the status of the fieldbus master
(online/offline/error etc.).
Check cable connections to the
EIA-485/X5 terminals 29, 30 and 31 on
the control unit.
A7EE Panel loss
Programmable warning:
49.05 Communication loss
action
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Check mounting platform if being used.
Disconnect and reconnect the control
panel.
A88F Cooling fan Maintenance timer limit
exceeded.
Consider changing the cooling fan.
Parameter 05.04 Fan on-time counter
shows the running time of the cooling
fan.
A8A0 AI supervision
Programmable warning:
12.03 AI supervision
function
An analog signal is outside the
limits specified for the analog
input.
Check signal level at the analog input.
Check the wiring connected to the input.
Check the minimum and maximum limits
of the input in parameter group 12
Standard AI.
A8A1 RO life warning The relay has changed states
more than the recommended
number of times.
Change the control unit or stop using the
relay output.
0001 Relay output 1 Change the control unit or stop using
relay output 1.
0002 Relay output 2 Change the control unit or stop using
relay output 2.
0003 Relay output 3 Change the control unit or stop using
relay output 3.
A8A2 RO toggle warning The relay output is changing
states faster than
recommended, e.g. if a fast
changing frequency signal is
connected to it. The relay
lifetime will be exceeded
shortly.
Replace the signal connected to the relay
output source with a less frequently
changing signal.
0001 Relay output 1 Select a different signal with parameter
10.24 RO1 source.
0002 Relay output 2 Select a different signal with parameter
10.27 RO2 source.
0003 Relay output 3 Select a different signal with parameter
10.30 RO3 source.
Code
(hex)
Warning / Aux. code Cause What to do