R6…R9 Quick installation guide 7
Ratings and fuses
IEC ratings at U
N
= 230 V, 400 V and 480 V
U
N
= 230 V
U
N
= 400 V
Type
ACS580
-01-
Input
rating
Output ratings
Max.
losses
Frame
size
Max.
current
Nominal use Light-duty use Heavy-duty use
I
1
I
max
I
N
P
N
I
Ld
P
Ld
I
Hd
P
Hd
A A A kW A kW A kW
W
3-phase U
N
= 230 V
144A-2 144 205 144 37 143 37 114 30 1035 R6
171A-2 171 257 171 45 169 45 143 37 1251 R7
213A-2 213 304 213 55 211 55 169 45 1521 R7
276A-2 276 380 276 75 273 75 211 55 2061 R8
3AXD00000586715.xls L
Type
ACS580-01-
Input ratings Output ratings Frame size
I
1
I
N
P
N
A
A
1)
kW
1-phase U
N
= 230 V
144A-2 137 68 18.5 R6
171A-2 153 80 22 R7
213A-2 209 104 30 R7
276A-2 258 130 37 R8
3AXD00000586715.xls L
1)
Continuous current, no overloadability
Type
ACS580
-01-
Input
rating
Output ratings Max.
losses
Frame
size
Max.
current
Nominal use Light-duty use Heavy-duty use
I
1
I
max
I
N
P
N
I
Ld
P
Ld
I
Hd
P
Hd
A A A kW A kW A kW
W
3-phase U
N
= 400 V
145A-4 145 178 145 75 138 75 105 55 2492 R6
169A-4 169 247 169 90 161 90 145 75 2536 R7
206A-4 206 287 206 110 196 110 169 90 3391 R7
246A-4 246 350 246 132 234 132 206 110 3945 R8
293A-4 293 418 293 160 278 160 246
1)
132 5174 R8
363A-4 363 498 363 200 345 200 293 160 6294 R9
430A-4 430 545 430 250 400 200 363
2)
200 8231 R9
3AXD00000586715.xls L