EasyManua.ls Logo

ABB ACS580-01 Series - Hardware Description; Product Overview; Layout and Mounting Position

ABB ACS580-01 Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
R6…R9 Quick installation guide 9
R0-
R3
R6-
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
uR or aR fuses
Type
ACS580
-01-
Min. short-
circuit
current
1)
Input
current
uR or aR (DIN 43620 blade style)
Nominal
current
I
2
t Voltage
rating
Bussmann
type
IEC 60269
size
A A A A
2
s V
3-phase U
N
= 230 V
144A-2 1000 144.0 315 46500 690 170M3817 1
171A-2 1280 171.0 450 105000 690 170M5809 2
213A-2 1450 213.0 500 155000 690 170M5810 2
276A-2 2050 276.0 630 220000 690 170M6810 3
3-phase U
N
= 400 or 480 V
145A-4 1280 145 315 46500 690 170M3817 1
169A-4 1800 169 450 105000 690 170M5809 1
206A-4 2210 206 500 145000 690 170M5810 1
246A-4 3010 246 630 275000 690 170M5812 2
293A-4 4000 293 800 490000 690 170M6812D 2
363A-4 5550 363 1000 985000 690 170M6814D 2
430A-4 7800 430 1250 2150000 690 170M8554D 2
3AXD00000586715.xls L
1)
Minimum short-circuit current of the installation
Type
ACS580
-01-
Min. short-
circuit
current
1)
Input
current
uR or aR (DIN 43653 bolted tags)
Nominal
current
I
2
t Voltage
rating
Bussmann
type
IEC 60269
size
A A A A
2
s V
3-phase U
N
= 400 or 480 V
145A-4 1000 145 250 28500 690 170M3016 1
169A-4 1280 169 315 46500 690 170M3017 1
206A-4 1520 206 350 68500 690 170M3018 1
246A-4 2050 246 450 105000 690 170M5009 2
293A-4 2200 293 500 145000 690 170M5010 2
363A-4 3100 363 630 275000 690 170M5012 2
430A-4 3600 430 700 405000 690 170M5013 2
3AXD00000586715.xls L
1)
Minimum short-circuit current of the installation

Other manuals for ABB ACS580-01 Series