8 R6…R9 Quick installation guide
U
N
= 480 V
gG fuses
Type
ACS580
-01-
Input
rating
Output ratings
Max.
losses
Air
flow
Frame
size
Max.
current
Nominal use Heavy-duty use
I
1
I
max
I
Ld
P
Ld
I
Hd
P
Hd
A A A kW hp A kW hp
W
m
3
/h
3-phase U
N
= 480 V
145A-4 124 178 124 75 100 96 55 75 1476 435 R6
169A-4 156 247 156 90 125 124 75 100 1976 450 R7
206A-4 180 287 180 110 150 156 90 125 2346 450 R7
246A-4 240 350 240 132 200 180 110 150 3336 550 R8
293A-4 260 418 260 160 200 240
1)
132 150 3936 550 R8
363A-4 361 542 361 200 300 302 160 250 4836 1150 R9
430A-4 414 542 414 250 350 361
2)
200 300 6036 1150 R9
3AXD00000586715.xls L
Type
ACS580-01-
Min. short-
circuit
current
1)
Input
current
gG (IEC 60269)
Nominal
current
I
2
t Voltage
rating
ABB type IEC
60269
size
A A A A
2
s V
3-phase U
N
= 230 V
144A-2 1700 144.0 200 300000 500 OFAF0H200 0
171A-2 2300 171.0 250 600000 500 OFAF0H250 0
213A-2 3300 213.0 315 710000 500 OFAF1H315 1
276A-2 5500 276.0 400 1100000 500 OFAF2H400 2
3-phase U
N
= 400 or 480 V
145A-4 1700 145 160 185000 500 OFAF00H160 00
169A-4 3300 169 250 600000 500 OFAF0H250 0
206A-4 5500 206 315 710000 500 OFAF1H315 1
246A-4 6400 246 355 920000 500 OFAF1H355 1
293A-4 7800 293 425 1300000 500 OFAF2H425 2
363A-4 9400 363 500 2000000 500 OFAF2H500 2
430A-4 10200 430 630 2800000 500 OFAF3H630 3
3AXD00000586715.xls L
1)
Minimum short-circuit current of the installation