112 Technical data
The calculated short-circuit current 2.7 kA is higher than the minimum short-circuit
current of the drive gG fuse type OFAF00H160 (2400 A). -> The 500 V gG fuse (ABB
Control OFAF00H160) can be used.
Fuse tables for frame sizes R5 and R6
Standard gG fuses
ACS800-01
size
Input
current
Min.
short-
circuit
current
Fuse
AA
A
2
s *
V Manufacturer Type IEC size
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0025-2 67 1050 80 34500 500 ABB Control OFAF000H80 000
-0030-2 81 1480 100 63600 500 ABB Control OFAF000H100 000
-0040-2 101 1940 125 103000 500 ABB Control OFAF00H125 00
-0050-2 138 2400 160 200000 500 ABB Control OFAF00H160 00
-0060-2 163 2850 200 350000 500 ABB Control OFAF1H200 1
-0070-2 202 3300 224 420000 500 ABB Control OFAF1H224 1
Three-phase supply voltage 380 V, 400 V or 415 V
-0040-3 69 1050 80 34500 500 ABB Control OFAF000H80 000
-0050-3 83 1480 100 63600 500 ABB Control OFAF000H100 000
-0060-3 100 1940 125 103000 500 ABB Control OFAF00H125 00
-0075-3 142 2400 160 200000 500 ABB Control OFAF00H160 00
-0070-3 ** 138 2400 160 200000 500 ABB Control OFAF00H160 00
-0100-3 163 2850 200 350000 500 ABB Control OFAF1H200 1
-0120-3 198 3300 224 420000 500 ABB Control OFAF1H224 1
-0135-3 221 3820 250 550000 500 ABB Control OFAF1H250 1
-0165-3 254 4510 315 1100000 500 ABB Control OFAF2H315 2
-0205-3 286 4510 315 1100000 500 ABB Control OFAF2H315 2
=
410 V
2 ·
(67.66 mohm)
2
+ (22.19 mohm + 13.94 mohm)
2
I
k2-ph
= 2.7 kA

Table of Contents