Operation
26
How to change the value of bit pointer parameter to fixed 0 (FALSE) or 1 (TRUE)
The bit pointer parameter can be fixed to constant value of 0 (FALSE) or 1 (TRUE).
When adjusting a bit pointer parameter on the control panel, CONST is selected in 
order to fix the value to 0 (displayed as C.FALSE) or 1 (C.TRUE).
For more information, see appropriate Firmware Manual.
Step Action Display
1. Go to the Main menu by pressing   if you are in the Output mode, otherwise 
by pressing   repeatedly until you get to the Main menu.
2. Go to the Parameters option by selecting PARAMETERS on the menu with 
keys   and  , and pressing  .
Select the appropriate parameter group with keys   and  . Here the 
bit pointer parameter 14.07 DI02 OUT SRC is used as an example.
 
3. Press   to select the appropriate parameter group. Select the appropriate 
parameter with keys   and  . Current value of each parameter is 
shown below its name.
4. Press   .
Select CONST with keys   and  . 
5. Press . 
6. Specify a new constant value (TRUE or FALSE) for the bit pointer parameter
with keys   and  .
MENU
EXIT
  
PARAMETERS 
ASSISTANTS
CHANGED PAR
EXIT ENTER00:00
MAIN MENU 1
LOC
ENTER
  
01 Actual values
02 I/O values
03 Control values
04 Appl values
06 Drive status
EXIT
SEL
00:00
PAR GROUPS 01
LOC
  
10 Start/stop/dir
11 Start/stop mode
12 Operating mode
13 Analogue inputs
14 Digital I/O
EXIT
SEL
00:00
PAR GROUPS 14
LOC
SEL
  
1401 DI01 Ton9901 
1405 DI01 Toff
1406 DI02 conf
1407 DI02 out src
        P.06.02.03
PARAMETERS
EXIT
EDIT
00:00
LOC
EDIT
  
  
1407 DI02 out src
  
  
  
PAR EDIT
   Pointer
CANCEL NEXT00:00
LOC
  
  
1407 DI02 out src
  
  
  
PAR EDIT
    Const
CANCEL NEXT00:00
LOC
NEXT
  C.FALSE
  
  
1407 DI02 out src
PAR EDIT
CANCEL
SAVE
00:00
[0]
LOC
  C.TRUE
  
  
1407 DI02 out src
PAR EDIT
CANCEL
SAVE
00:00
[1]
LOC