Parameters 381
50.56 FBA B comm
supervision force
Activates fieldbus communication monitoring separately for
each control location (see section Local control vs. external
control on page 24).
The parameter is primarily intended for monitoring the
communication with FBA B when it is connected to the
application program and not selected as a control source by
drive parameters.
0000b
0000b…0111b FBA B communication monitoring selection. 1 = 1
51
51 FBA A settings
Fieldbus adapter A configuration.
51.01 FBA A type Displays the type of the connected fieldbus adapter module.
0 = Module is not found or is not properly connected, or is
disabled by parameter 50.01 FBA A enable; 1 = FPBA;
32 = FCAN; 37 = FDNA; 101 = FCNA, 128 = FENA-11/21;
135 =FECA; 136 =FEPL; 485 = FSCA.
This parameter is read-only.
-
51.02 FBA A Par2 Parameters 51.0251.26 are adapter module-specific. For
more information, see the documentation of the fieldbus
adapter module. Note that not all of these parameters are
necessarily in use.
-
0…65535 Fieldbus adapter configuration parameter. 1 = 1
……
51.26 FBA A Par26 See parameter 51.02 FBA A Par2.-
0…65535 Fieldbus adapter configuration parameter. 1 = 1
51.27 FBA A par refresh Validates any changed fieldbus adapter module configuration
settings. After refreshing, the value reverts automatically to
Done.
Note: This parameter cannot be changed while the drive is
running.
Done
Done Refreshing done. 0
Refresh Refreshing. 1
51.28 FBA A par table ver Displays the parameter table revision of the fieldbus adapter
module mapping file (stored in the memory of the drive).
In format axyz, where ax = major table revision number; yz =
minor table revision number.
This parameter is read-only.
-
Parameter table revision of adapter module. -
51.29 FBA A drive type
code
Displays the drive type code in the fieldbus adapter module
mapping file (stored in the memory of the drive).
This parameter is read-only.
-
0…65535 Drive type code stored in the mapping file. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Value
0 Ext 1 1 = Communication monitoring active when Ext 1 is being used.
1 Ext 2 1 = Communication monitoring active when Ext 2 is being used.
2 Local 1 = Communication monitoring active when local control is being
used.
3…15 Reserved