35
1SDH000760R0002, L4106
Installation and operating instructions, ATS022
Modbus
Communication protocol. User can set Address, Baud Rate, Stop Bits and Parity for the Modbus.
Address means the Modbus address of the device. The address can be chosen between 1 … 247. The
Baud Rate can be 9600 –19200 – 38400 kbps. Stop bit can be set 0 or 1 and the parity can be set even,
odd or none. Factory settings are Modbus address 1, Modbus Baud Rate 9600, Modbus Stop Bit 1 and
Modbus Parity None.
Tx/Rx LED indicates data transmission: LED is ON only when data is transmitted from the ATS022.
Figure 8.19 Modbus
Language Selection
In this page it is possible to choose the language. The choices are English, French, Italian, Spanish,
Finnish and German. Factory setting is English.
8. Using automatic transfer switch ATS022
Deutch
Cancel
Ok
Edit
Language Selection
KA00479
Figure 8.20 Language selection, English as default
Change Password
In this page it is possible to change password. The password consists of four numbers. In this page it is
always shown as 0000. New password is set by using UP, DOWN and ENTER keys.
Figure 8.21 Change the password