EasyManua.ls Logo

ABB AX521

ABB AX521
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTICE!
Risk of damage to I/O modules!
Do not perform hot swapping if any I/O module with firmware version lower than
3.0.14 is part of the I/O configuration.
For min. required device index see table below.
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed
or inserted during operation.
Device Min. required device index for I/O module as of
FW Version 3.0.14
AI523 (-XC) D2
AI531 D4
AI531-XC D2
AI561 B2
AI562 B2
AI563 B3
AO523 (-XC) D2
AO561 B2
AX521 (-XC) D2
AX522 (-XC) D2
AX561 B2
CD522 (-XC) D1
DA501 (-XC) D2
DC522 (-XC) D2
DC523 (-XC) D2
DC532 (-XC) D2
DC561 B2
DC562 A2
DI524 (-XC) D2
DI561 B2
DI562 B2
DI571 B2
DI572 A1
DO524 (-XC) A3
DO526 A2
DO526-XC A0
DO561 B2
DO562 A2
DO571 B3
DC522
2019/11/15 3ADR024117M02xx, 11, en_US 135

Table of Contents

Related product manuals