… 6  Electrical connections 
 
Installing the connection cables 
 
General information on cable installation 
Ensure that a drip loop (water trap) is used when installing the 
connecting cables for the sensor. 
When mounting the sensor vertically, position the cable entries 
at the bottom.  
If necessary, rotate the transmitter housing accordingly. 
 
 
1 Drip loop 
 
Figure 27:  Laying the connection cable 
 
 
 
 
 
 
Signal cable specification 
 
The signal cable used for the connection of the transmitter and 
sensor must fulfill at least the following technical specifications. 
 
Cable specification 
Impedance  100 to 120 Ω 
Withstand voltage  120 V 
Outer diameter  6 to 12 mm (0.24 to 0.47 in) 
Cable design  Two wire pairs as a star-quad cable 
Conductor cross-section  Length-dependent 
Shield  Copper braid with approximately 85 % coverage 
Temperature range  Application-dependent, for use in potentially 
explosive atmospheres, observe the information 
in Temperature resistance for the connecting 
cable on page 13! 
 
Maximum signal cable length 
0.25 mm
2
 (AWG 24)  50 m (164 ft)
0.34 mm
2
 (AWG 22)  100 m (328 ft)
0.5 mm
2
 (AWG 20)  150 m (492 ft)
0.75 mm
2
 (AWG 19)  200 m (656 ft)
 
Recommended cables 
It is recommended to use an ABB signal cable for standard 
applications. The ABB signal cable fulfills the above-mentioned 
cable specification and can be utilized unrestrictedly up to an 
ambient temperature of T
amb.
 = 80 °C (176 °F). 
 
ABB signal cable  Ordering number
5 m (16 ft)  3KQZ407123U0500
10 m (33 ft)  3KQZ407123U1000
20 m (65 ft)  3KQZ407123U2000
50 m (164 ft)  3KQZ407123U5000
100 m (328 ft)  3KQZ407123U1H00
150 m (492 ft)  3KQZ407123U1F00
200 m (656 ft)  3KQZ407123U2H00
 
For marine applications, an appropriate certified signal cable 
must be used.  
ABB recommends the cable HELKAMA RFE-FRHF 
2×2×0,75 QUAD 250V (HELKAMA order number 20522).