14 CoriolisMaster FCB400, FCH400 CORIOLIS MASS FLOWMETER | OI/FCB400/FCH400-EN REV. E
… 2 Use in potentially explosive atmospheres
… Temperature data
Measuring medium temperature for sensors in integral mount design with single-compartment housing
Model FCx4xx-A2… and FCx4xx-F2… in Zone 2, Division 2
The table shows the maximum permissible measuring medium temperature as a function of ambient temperature and temperature
class.
Temperature class
Ambient temperature T
amb.
T1 T2 T3 T4 T5 T6
30 °C ( 86 °F) 205 °C (400 °F) 205 °C (400 °F) 195 °C (383 °F) 130 °C (266 °F) 95 °C (203 °F) 80 °C (176 °F)
40 °C ( 104 °F) 205 °C (400 °F) 205 °C (400 °F) 195 °C (383 °F) 130 °C (266 °F) 95 °C (203 °F)
50 °C ( 122 °F) 205 °C (400 °F) 205 °C (400 °F) 195 °C (383 °F) 130 °C (266 °F) 95 °C (203 °F)
60 °C ( 140 °F) 205 °C (400 °F) 205 °C (400 °F) 195 °C (383 °F) 130 °C (266 °F)
70 °C ( 158 °F) 205 °C (400 °F) 205 °C (400 °F) 195 °C (383 °F) 130 °C (266 °F)
* Only with the ‘Extended tower length – TE1, TE2 or TE3’ order option