9 CP620, CP630, CP635, CP651, CP661, CP665, CP676
Electromagnetic Compatibility (EMC)
Test executed on the 230 V AC side of the Power Supply (EN 61000-4-11).
Parameter Value According to
Radiated disturbance test Class A EN 55011
Electrostatic discharge im-
munity test
8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
EN 61000-4-2
Radiated, radio-frequency,
electromagnetic field immuni-
ty test
80 MHz … 1 GHz, 10 V/m
1.4 GHz … 2 GHz, 3 V/m
2 GHz … 2.7 GHz, 1 V/m
EN 61000-4-3
Burst immunity test ± 2 kV DC power port
± 1 kV signal line
EN 61000-4-4
Surge immunity test ± 0.5 kV DC power port (line to earth)
± 0.5 kV DC power port (line to line)
± 1 kV signal line (line to earth)
EN 61000-4-5
Immunity to conducted dis-
turbances inducted by radio-
frequency field
0.15 … 80 MHz, 10 V EN 61000-4-6
Voltage dips, short interrup-
tions and voltage variations
immunity test
Port: AC mains. Level:
100 % / duration: 1 cycle and 250 cycles (50 Hz);
40 % / duration: 10 cycles (50 Hz);
70 % / duration: 25 cycles (50 Hz);
Phase: 0°-180°