EasyManua.ls Logo

ABB CP 600 Series - Electromagnetic Compatibility (EMC)

ABB CP 600 Series
29 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 CP620, CP630, CP635, CP651, CP661, CP665, CP676
Electromagnetic Compatibility (EMC)
Test executed on the 230 V AC side of the Power Supply (EN 61000-4-11).
Parameter Value According to
Radiated disturbance test Class A EN 55011
Electrostatic discharge im-
munity test
8 kV (air electrostatic discharge)
4 kV (contact electrostatic discharge)
EN 61000-4-2
Radiated, radio-frequency,
electromagnetic field immuni-
ty test
80 MHz … 1 GHz, 10 V/m
1.4 GHz … 2 GHz, 3 V/m
2 GHz … 2.7 GHz, 1 V/m
EN 61000-4-3
Burst immunity test ± 2 kV DC power port
± 1 kV signal line
EN 61000-4-4
Surge immunity test ± 0.5 kV DC power port (line to earth)
± 0.5 kV DC power port (line to line)
± 1 kV signal line (line to earth)
EN 61000-4-5
Immunity to conducted dis-
turbances inducted by radio-
frequency field
0.15 … 80 MHz, 10 V EN 61000-4-6
Voltage dips, short interrup-
tions and voltage variations
immunity test
Port: AC mains. Level:
100 % / duration: 1 cycle and 250 cycles (50 Hz);
40 % / duration: 10 cycles (50 Hz);
70 % / duration: 25 cycles (50 Hz);
Phase: 0°-180°

Related product manuals