Page #50 background image
L2234
Emax
49/158
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000460R0002
L2778
Protection
Disabling
Disabling of
TRIP only
Zone selectivity
Start-up threshold
Thermal memory
Trip Threshold Trip time
tolerance
(2)
Trip Time
Trip
threshold
tolerance
(2)
13.2.9.12 Summary table of the protection function settings for the PR122/P
(1)
The minimum value of this trip is 1s regardless of the type of curve set (self-
protection).
(2)
These tolerances are based on the following assumptions:
- self-supplied relay at full power (without start-up)
- presence of auxiliary power supply
- two-phase or three-phase power supply
- preset trip time 100 ms.
(3)
no-trip time
(4)
the protection G is disabled for current values greater than 4In, where I4 < 0.5 In,
greater than 6 In, where 0.5 In I4 < 0.8 In and greater than 8 In where I40.8 In.
(5)
Max trip time
For all cases not covered by the above hypotheses, the following tolerance values
apply:
Protections Trip threshold Trip time
L Release between 1.05 and 1.25 x I1 ± 20%
S ± 10% ± 20%
15% 60ms
G ± 10% ± 20%
Others ± 20%
L
(t=k/i
2
) curve  0.4xIn
I
1
1xIn 3 s t
1
144 s
(1)
, step 3s
Release between
± 10%, I
g
6In
IEC 60255-3 step 0.01xIn t1@ 3I
1
1.05 and1.2 xI1
± 20%, I
g
> 6In
S  0.6 xIn I
2
10xIn 0.05 s t
2
0.8 s, step 0.01s ± 7%,I
g
6 In The best of the two data
(t=k) step 0.1xIn 0.10 s t
2 start-up
30 s, step 0.01s ± 10%,I
g
> 6 In ± 10% or 40 ms
0.6 xIn I
2 start-up
10xIn 0.04 s t
2 sel
0.20 s, step 0.01s
step 0.1xIn
S  0.6xIn
I
2
10xIn 0.05 s t
2
0.8 s, ± 7%,I
g
6 In ± 15%, I
g
6In
(t=k/i
2
) step 0.1xIn step 0.01s at 10xIn ± 10%,I
g
> 6 In ± 20%, I
g
> 6In
I  1,5xIn I
3
15xIn 30ms
(t=k) step 0.1xIn 0.10 s t
2 start-up
30 s, step 0.01s ± 10%
where I>I4
MCR  6.0xIn I
5
15xIn 30ms
(3)
± 10%
(t=k) step 0.1xIn
G
(4)
 0.20xIn I
4
1xIn 0.1 s t
4
1 s, step 0.05s The best of the two data
(t=k) step 0.02xIn 0.1 s t
4 start-up
30s, step 0.01s ± 7% ± 10% or 40 ms
0.04 s t
4 sel
0.2 s, step 0.01s
where I>I4
G
(4)
 0.20xIn I
4
1xIn 0.1 s t
4
1 s, step 0.05s ± 7% ± 15%
(t=k/i
2
)
step 0.02xIn 0.10 s t
2 start-up
30s, step 0.01s
@I
g
>4In
Gext  0.20xIn I
4
1xIn 0.1 s t
4
1s, step 0.05s The best of the two data
(t=k) step 0.02xIn 0.1 s t
4 start-up
1.5s, step 0.01s ± 7% ± 10% or 40 ms
0.20xIn I
4
1xIn 0.04 s t
4 sel
0.2s, step 0.01s
step 0.02xIn where I>I4
Gext  0.20xIn I
4
1xIn 0.1s t
4
1s, step 0.05s ± 7% ± 15%
(t=k/i
2
) step 0.02xIn @I
g
>4In
Rc
Idn =3.0-5.0-7.0-10-20
0.06-0.10-0.20-0.30-0.40-0.50 140ms@0.06s
(5)
(Idn) -30A 0.80s
(3)
0 ÷ 20% 950ms@0.80s
(5)
U  2% I
6
90% %Unb. 0.5s t
6
60 s, step 0.5s ± 10% The best of the two data
(t=k) step 1% ± 10% or 40 ms
OT  Fixed, defined by Instantaneous ± 5°C - - -
(temp=k) SACE
Iinst  Automatic, defined Instantaneous
by SACE
LC1/LC2 loads  50%÷100% step 0.05xI
1
control
Warning Iw  0,3÷10I
n
step 0,05xI
n
± 10% 10÷40 ms

Table of Contents