10. Transceiver error codes
Error
code
Description Suggested cause and action
01
System error
The transceiver could not perform the
requested task. Turn off the transceiver and
restart. Attempt with individual readings
rather than total reading (if this was the
case). If the error persists, a serious inter-
nal fault may have occured. Contact your
EXCOUNT-II service representative.
11
Prohibited action
The user has attempted to do something which
is prohibited. For example, it is not permitted to
re-transmit an already successful transmission.
Turn off the transceiver and restart.
21
Checksum error
An error occurred in the data transmission
and the data has been lost or corrupted.
Interference from a nearby high-frequency
source can be a likely cause. Wait 30
seconds before attempting to retransmit the
data. Attempt with individual readings rather
than total reading (if this was the case).
31
EEPROM data read error
The transceiver could not read from the inter-
nal EEPROM memory. Turn off the transceiver
and restart. If the error persists a serious
internal fault may have occured. Contact your
EXCOUNT-II service representative.
32
EEPROM data write
error
The transceiver could not write to the inter-
nal EEPROM memory. Turn off the transcei-
ver and restart. If the error persists, contact
your EXCOUNT-II service representative.
41
Low temperature
The ambient temperature is lower than defi-
ned in the database for resistive current mea-
surements, (lowest defined temperature is -10
º C). Take measurements at another time.
42
High temperature
The ambient temperature is higher than
defined in the database for resistive current
measurements, (highest dened temperature is
+60 º C). Take measurements at another time.