EasyManua.ls Logo

ABB HF Series - Page 42

ABB HF Series
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42 ELECTRONIC COMPACT STARTER | MANUAL
Group mounting fused design
Group mounting HF-starters results in significant space savings in control cabinets. Please find all installation proposals in
table 21 for 500 V AC and in table 22 for 415 V AC.
HF-Starter Iq
[kA]
SCPD Max. Current
[A]
Max. Voltage
[V AC]
HF0.6 35 Fuse 25 A gG 25 500
HF2.4 35 Fuse 25 A gG 25 500
HF9 35 Fuse 25 A gG 25 500
Table 21 Type 1 coordination of HF-Starter with Fuse 25 A gG at 500 V AC
HF-Starter Iq
[kA]
SCPD Max. Current
[A]
Max. Voltage
[V AC]
HF0.6 50 Fuse 25 A gG 25 415
HF2.4 50 Fuse 25 A gG 25 415
HF9 50 Fuse 25 A gG 25 415
Table 22 Type 1 coordination of HF-Starter with Fuse 25 A gG at 415 V AC
Short-circuit protection for use in UL market
For single or group protection the following fuses can be used for UL application according to UL 60947-1/-4-1 Type 1 coordi-
nation.
HF-Starter FLA
[A / V AC]
Iq
[kA]
SCPD Max. current
[A]
Max. Voltage
[V AC]
HF0.6 0.6 / 500 100 Fuse class J or CC 30 480
HF2.4 2.4 / 500 100 Fuse class J or CC 30 480
HF9 6.5 / 500 100 Fuse class J or CC 30 480
HF0.6 0.6 / 500 5 Fuse RK 5 20 480
HF2.4 2.4 / 500 5 Fuse RK 5 20 480
HF9 6.5 / 500 5 Fuse RK 5 20 480
Table 23 Type 1 coordination of HF-Starter with fuses according to UL60947-1/-4-1