Specifications (Refer to LMT100/200 Datasheets for Details)
Electronic transmitter:
Repeatability ± 0.005% of Full Scale or 0.305 mm (0.012 in), whichever is greater
Non-linearity ± 0.01% of Full Scale or 0.864 mm (0.034in), whichever is greater
Measuring accuracy ± 0.01% of Full Scale or 1.27 mm (0.050 in), whichever is greater
Supply voltage 12 to 42 Vdc - 4-20mA HART loop powered
Output/Communications 4-20mA HART7®
User Interface Interactive display, DTM, EDDL with NE107 messaging
Power consumption 4-20mA at 36.0 Vdc - 3.6mA 0.13 watts; 21mA 0.76 watts
at 12.0 Vdc - 3.6mA 0.043 watts; 21mA 0.25 watts
HART mode (4.0mA) at 36.0 Vdc 0.144 watts
at 12.0 Vdc 0.048 watts
Ambient temperature -40 to 85°C (-40 to 185°F) Ambient
Humidity 0 to 100% RH
Electrical connection Two M20 x 1.5 or two 1/2in. FNPT, adapters and bus connectors also available
Ingress protection IP66, NEMA 4X
Sensor tube:
Material 316/L Stainless Steel
Process temperature LMT100: -195.5 to 121.1°C (-320 to 250°F)
Process pressure LMT100: -1.0 to 124.1 bar @ 149°C (-14.7 to 1800 psig @ 300°F)
Probe length LMT100: 304.8mm to 9.14m (1 to 30ft) / LMT200: 304.8mm to 15.24m (1 to 50ft)
Figure 3 LMT General Model
6 in. (152.4mm) minimum
See dimensional drawings
Top of vessel
ML
L1 = Unmeasured
Highest
measurable
level
IL - Insertion length
distance from bottom of
process connection to the
end of the probe
L2 = Unmeasured
Lowest
measurable level
No minimum
float separation
PL - Probe length depends
on process temperature
Compression
Fitting Option