LMT SERIES | MAGNETOSTRICTIVE LEVEL TRANSMITTER LMT100 & 200 MODELS | CI/LMT100/200-EN REV. B
5
3 Easy Setup
1 Log on to the LMT at the Standard or Advanced access level.
2 Select Easy Setup in the main menu.
3 Select a language in the “Easy Setup” menu and press .
4 Select available option of primary variable in the “Easy
Setup” menu and press
.
5 Select available option of units of measure in the “Easy
Setup” menu and press
.
6 Set LRV in the “Easy Setup” menu and press .
LRV is the lower range value which corresponds to 4 mA current
out value.
7 Set URV in the “Easy Setup” menu and press .
URV is the upper range value which corresponds to the 20 mA
current out value.
8 Set Damping time in the “Easy Setup” menu and press .
Damping allows smoothing step response in the device output.
9 Select displayed variable in the “Easy Setup” menu and
press
.
Sets the selected process variable on the first line on the
process display.
10 Set a tag in the “Easy Setup” menu and press .
A tag is a quick way to identify the device.
*For detailed commission/operation steps refer to LMT
operating instructions.