58  M OT O R  CO N TR O L A N D   PR OT E C TI O N  U N IT   M1 0 X U SE R G U I D E
—
47 Restart (2xdip<200ms within 1sec)
Enhanced Mode
In the enhanced mode, the reaction of the 
autorestart function not only depends on the 
length of the voltage dip, but also the number of 
voltage dips within a short period of time.
Enhanced mode includes all 3 cases listed in stan-
dard mode. In addition, case 4 is supported.  
Case 4: 2xdip<200ms within 1sec
Under case 4 scenario, two voltages dips may 
occur within 1 seconds. Each dip is shorter than 
200ms. The device shall be able to react and trig-
ger a delay restart after the second voltage dip 
recovers. 
Failsafe functionality
M10x failsafe function supervises the communi-
cation network interface and connection to the 
remote devices controlling the motor/starter 
equipment. The network supervision on M10x is 
based on no data exchange detected within the 
pre-configured delay time (1~25s)  which may be 
different from the network supervision on control 
system level.
If the device falls into failsafe mode, the pre-
configured failsafe action will be followed. The 
options of the failsafe action are,
-  Motor stay as it is ( No operation);
-  Start the motor (Start 1);
-  Start the motor in reverse direction (Start2);
-  Trip the motor (Trip).
Under failsafe mode, the motor control access falls 
to local control regardless of previous settings. 
Both control from hardwiring (to local control
panel or on starter) and MDx panel are active under 
failsafe mode. Once the network is restored, the 
control access recovers to the previous setting, the 
tripping message 'communication failure'  is 
automatically reset.
To disable the network supervision 
function from M10x, set the communica-
tion failure delay time as '255"