The services of the PROFIBUS data link layer 
(Layer 2) are used by PROFIBUS-DP through
service access Points (SAPs). Precisely de-
fined functions are assigned to individual 
SAPs. For further information on SAPs, refer 
to the PROFIBUS master manual.
The following SAPs are supported by the M10x:
  • SAP47 – acyclic read/write of MSAC_C2, abort
  • SAP48 – acyclic read/write of MSAC_C2, abort
  • SAP49 – initiate req of MSAC_C2
  • SAP51 – acyclical read/write of MSAC_C1
  • SAP56 – read input
  • SAP57 – read output
  • SAP58 – global control command
  • SAP59 – read configuration data
  • SAP60 – read diagnosis data
  • SAP61 – initial parameters
  • SAP62 – check the configuration data
For more information on PROFIBUS 
implementation in M10x, please refer to 
M10x-P PROFIBUS protocol 
implementation.
63 Bus (line) network
PROFIBUS description
PROFIBUS-DP is a distributed I/O system that 
enables the master to use a large number of 
peripheral modules and field devices. The 
data transfer is mainly cyclic: the master 
reads the 
input information from the slaves and sends 
the output information back to the slaves. 
PROFIBUS-DPV1 is an extension of the DP pro-
tocol. 
Additionally, it allows the acyclic exchange of 
data between master station and slave sta-
tion.
88                                            M OTO R CO NTRO L A N D PROTE C TI O N U N IT M10X USER G U I D E