Relates to
Message
Motor Starter System
Alarm condition Trip condition
Location
Supervision
X n.a. MControl inserted in wrong
location (other than
specified)
Suggested action:
check expected "MControl
Location" settings in
MNavigate -> Reports ->
Topology -> Network View
and compare with actual
address setting in cubicle
/ rotary switch of Control
Condapter
If MControl has been
moved from another
location then Download
MControl
Application/Parameter/
Configuration
Motor Still Running X (X) X n.a. Contactor feedback after
OFF command ok, but
current still detected
Suggested action:
Check / Replace Power
Module
Unexpected Feeder
Current
X (X) n.a. Contactor feedback after
OPEN command ok, but
current detected
Suggested action:
Check / Replace Feeder
Module
Welded X n.a. Contactor feedback after
OFF command missing and
current detected
Suggested action:
Switch Main switch to
OFF
Check / Replace Power
Module