Relates to
Message
Moto
r
Starter System
Alarm condition Trip condition
X
Measured contact
temperature
T is higher than
the parameterized Alarm
level.
Suggested action:
Check Power Module
contacts
Investigate root cause for
overheating
Check MNS Service
Manual for details
Measured contact
temperature
T is higher than
the parameterized Trip level.
Suggested action:
Check Power Module
contacts
Investigate root cause for
overheating
Check MNS Service
Manual for details
Contact
T
emperature
Supervision
(L1,L2,L3)
X n.a.
One of the fuses blown
Suggested action:
Check fuses
Investigate root cause for
blown fuse
Fuse Supervision
(L1,L2,L
3)
Switch Cycle
Supervision
(K1,K2,K3)
X
Number of switching cycles
for contactor K1 / K2 / K3
has exceeded the
parameterized Alarm level
Suggested action:
Module maintenance
Note:
To reset the Alarm
message:
Increase the parameter
value
Download parameters to
MControl
n.a.